Section 3 1MAC306892-MB C
Vendor-specific implementation
14 RER620
Communication Protocol Manual
3.2.1 Configuring IEC 60870-5-101
To configure one protocol instance to work as IEC 60870-5-101 slave, configure the
parameters to enable basic communication.
Port
According to the physical wiring, set either to "IEC101-COM1" or "IEC101-
COM2". Set the correct serial mode and communication baud rate under COM1/
COM2 settings.
Device Address
Set to match the address set in the master.
ASDU Address
Usually ASDU Address is the same as link address.
Link Mode
If the system is configured to use unbalanced communication, set Link Mode to
"Unbalanced". Otherwise, no change is needed.
COT Length
Usually set to 1. This setting must have the same value in the master and slave
devices.
IOA Length
Usually, set to 2. This setting must have the same value in the master and slave
devices.
Link Address Length
Usually set to 1. This setting must have the same value in the master and slave
devices.
ASDU Address Length
Usually set to 1. This setting must have the same value in the master and slave
devices.
3.2.2 Configuring IEC 60870-5-104
To configure one protocol instance to work as IEC 60870-5-104 server, configure the
parameters to enable basic communication.
Port
Set to "IEC104 - Ethernet".
Client IP
Set to match the IP address of the client device.
ASDU Address
Set to match the address set in the master.
ICheck the communication card jumpers. Refer to applicable manual for
details.