EasyManua.ls Logo

ABB RER620 - Cyclical Period; Transmit Window; Receive Window; Transmit Timeout

ABB RER620
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MAC306892-MB C Section 3
Vendor-specific implementation
RER620 23
Communication Protocol Manual
3.6.20 Cyclical period
• Min: 1
• Max: 604800
• Default: 10
• Unit: seconds
Cyclical period is the periodical timer for the cyclical data sending. The maximum of
604800 seconds means one week.
3.6.21 Transmit window
• Min: 1
• Max: 32767
• Default: 12
•Unit: APDU
The value of k shall indicate the maximum number of sequentially numbered I format
APDUs that the DTE may have outstanding (i.e. unacknowledged) at a given time. The
transmitter stops the transmission at k unacknowledged I format APDUs.
3.6.22 Receive window
• Min: 1
• Max: 32767
• Default: 8
•Unit: APDU
The receiver acknowledges at the latest after receiving w I format APDUs
Recommendation: w should not exceed two-thirds of k.
3.6.23 Transmit timeout
• Min: 1000
• Max: 255000
• Default: 15000
•Unit: ms
t1 is the timeout of a sent U-frame or I-frame. t1 starts after a U-frame or I-frame message
is sent. When t1 timer expires and no ACK for that message was received, the connection
termination (active close) will be initiated. The accuracy for t1 is 1 second. The timeout
setting should be set as a multiple of 1000ms.
3.6.24 Receive timeout
• Min: 1000

Table of Contents