EasyManua.ls Logo

ABB RER620 - Process information in control direction; System information in monitor direction; System information in control direction; Parameter in control direction

ABB RER620
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 3 1MAC302441-MB A
IEC 60870-5-101/104 protocol implementation
44 RER620
Point List Manual
Process information in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
System information in monitor direction
(station-specific parameter, mark with an “X” if it is only used in the standard direction,
“R” if only used in the reverse direction, and “B” if used in both directions)
System information in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
Parameter in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
File transfer
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
X
<45> := Single command C_SC_NA_1
X
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := Bitstring of 32 bit C_BO_NA_1
<70> := End of initialization M_EI_NA_1
X
<100> := Interrogation command C_IC_NA_1
X
<101> := Counter interrogation command C_CI_NA_1
<102> := Read command C_RD_NA_1
X
<103> := Clock synchronization command C_CS_NA_1
<104> := Test command C_TS_NB_1
<105> := Reset process command C_RP_NC_1
X
<106> := Delay acquisition command C_CD_NA_1
<110> := Parameter of measured value, normalized value P_ME_NA_1
<111> := Parameter of measured value, scaled value P_ME_NB_1
<112> := Parameter of measured value, short floating point value P_ME_NC_1
<113> := Parameter activation P_AC_NA_1
<120> := File ready F_FR_NA_1
<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory F_DR_TA_1

Other manuals for ABB RER620