EasyManua.ls Logo

ABB RER620 - Type identification and cause of transmission assignments

ABB RER620
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MAC302441-MB A Section 3
IEC 60870-5-101/104 protocol implementation
RER620 45
Point List Manual
Type identification and cause of transmission assignments
(station-specific parameters)
Shaded boxes are not required.
Blank = function or ASDU is not used.
Mark type identification/cause of transmission combinations:
“X” if used only in the standard direction;
“R” if used only in the reverse direction;
“B” if used in both directions.
Type identification
Cause of transmission
periodic, cyclic
background scan
spontaneous
initialized
request or requested
activation
activation confirmation
deactivation
deactivation confirmation
activation termination
return info caused by a remote cmd
return info caused by a local cmd
file transfer
interrogated by group <number>
request by group <n> counter request
unknown type identification
unknown cause of transmission
unknown common address of ASDU
unknown information object address
12345678910111213
20
to
36
37
to
41
44 45 46 47
<1> M_SP_NA_1
X X X
<2> M_SP_TA_1
X X
<3> M_DP_NA_1
X X X
<4> M_DP_TA_1
X X
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1
XX
X X
<10> M_ME_TA_1
X X
<11> M_ME_NB_1
XX
X X
<12> M_ME_TB_1
X X
<13> M_ME_NC_1
XX
X X
<14> M_ME_TC_1
X X
<15> M_IT_NA_1
X
<16> M_IT_TA_1
X
<17> M_EP_TA_1
<18> M_EP_TB_1
X
<19> M_EP_TC_1
X
<20> M_PS_NA_1
<21> M_ME_ND_1
XX
X X
<30> M_SP_TB_1
X X XX
<31> M_DP_TB_1
X X XX
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
X X
<35> M_ME_TE_1
X X

Other manuals for ABB RER620