112
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
NEF1INST CBFP signal from Io>>> stage A *) 85 0 2 1
NEF1LOW START signal from Io> stage A 160 67 1 2 1,9
NEF1LOW TRIP signal from Io> stage A 160 92 0 2 1
NEF1LOW CBFP signal from Io> stage A *) 85 0 2 1
NOC3HIGH START signal from 3I>> stage P 162 94 1 1 1,9
NOC3HIGH TRIP signal from 3I>> stage A 160 91 0 2 1
NOC3HIGH CBFP signal from 3I>> stage A *) 85 0 2 1
NOC3INST START signal from 3I>>> stage P 162 96 1 1 1,9
NOC3INST TRIP signal from 3I>>> stage P 162 98 0 1 1
NOC3INST CBFP signal from 3I>>> stage A *) 85 0 2 1
NOC3LOW START signal from 3I> stage A 160 84 1 2 1,9
NOC3LOW TRIP signal from 3I> stage A 160 90 0 2 1
NOC3LOW CBFP signal from 3I> stage A *) 85 0 2 1
NOC3LowB START signal from 3I> stage P 253 101 1 1 1,9
NOC3LowB TRIP signal from 3I> stage P 253 111 0 1 1
NOC3LowB CBFP signal from 3I> stage A *) 85 0 2 1
NPS3High START signal from I2>> stage P 21 91 1 1 1,9
NPS3High TRIP signal from I2>> stage P 21 94 0 1 1
NPS3High CBFP signal from I2>> stage A *) 85 0 2 1
NPS3Low START signal from I2> stage P 21 84 1 1 1,9
NPS3Low TRIP signal from I2> stage P 21 90 0 1 1
NPS3Low CBFP signal from I2> stage A *) 85 0 2 1
OE1High START signal from U/f >> P 253 103 1 1 1,9
OE1High TRIP signal from U/f >> P 253 113 0 1 1
OE1High CBFP signal from U/f >> A *) 85 0 2 1
OE1Low START signal from U/f > P 253 102 1 1 1,9
OE1Low TRIP signal from U/f > P 253 112 0 1 1
OE1Low CBFP signal from U/f > A *) 85 0 2 1
OV3HIGH START signal from 3U>> stage P 165 94 1 1 1,9
OV3HIGH TRIP signal from 3U>> stage P 165 91 0 1 1
OV3LOW START signal from 3U> stage P 165 84 1 1 1,9
OV3LOW TRIP signal from 3U> stage P 165 90 0 1 1
PSV3St1 START signal from U2>, stage 1 P 179 1 1 1 1,9
PSV3St1 START signal from U1<, stage 1 P 179 2 1 1 1,9
PSV3St1 START signal from U1>, stage 1 P 179 3 1 1 1,9
PSV3St1 TRIP signal from U2>, stage 1 P 179 4 0 1 1
PSV3St1 TRIP signal from U1<, stage 1 P 179 5 0 1 1
PSV3St1 TRIP signal from U1>, stage 1 P 179 6 0 1 1
PSV3St2 START signal from U2>, stage 2 P 180 1 1 1 1,9
PSV3St2 START signal from U1<, stage 2 P 180 2 1 1 1,9
PSV3St2 START signal from U1>, stage 2 P 180 3 1 1 1,9
PSV3St2 TRIP signal from U2>, stage 2 P 180 4 0 1 1
PSV3St2 TRIP signal from U1<, stage 2 P 180 5 0 1 1
PSV3St2 TRIP signal from U1>, stage 2 P 180 6 0 1 1
REF1A TRIP signal of dIo>, REF1A P 253 125 0 1 1
REF1A CBFP signal of REF1A A *) 85 0 2 1
REF4A START signal of REF4A P 253 106 1 1 1,9
REF4A TRIP signal of REF4A P 253 116 0 1 1
REF4A CBFP signal of REF4A A *) 85 0 2 1
REF4B START signal of REF4B P 253 110 1 1 1,9
REF4B TRIP signal of REF4B P 253 120 0 1 1
Table 10.6.-1 Class 1 data signals
Function block
name
Event St Ftyp
Inf
Num
GI Typ COT