EasyManua.ls Logo

ABB RET 541 - High-Speed Double-Pole Power Outputs (HSPO)

ABB RET 541
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
5.1.8.1. High-speed double-pole power outputs (HSPO)
The high-speed power outputs PS1_4_HSPO1... PS1_4_HSPO5 and
PS2_4_HSPO1...PS2_4_HSPO7 can be connected as double-pole outputs where the
object to be controlled (e.g. a circuit breaker) is electrically connected between the
two relay contacts, see the figure below. The high-speed double-pole power output
is recommended to be used for tripping purposes.
When TCS is used (see Table 5.1.8-1 on page 48), the outputs are
connected as shown in Figure 5.1.11.-1 on page 66.
cbcoil_b
Fig. 5.1.8.1.-1 High-speed double-pole power outputs (HSPO)
The high-speed power outputs PS1_4_HSPO1... PS1_4_HSPO5 and
PS2_4_HSPO1...PS2_4_HSPO7 can also be connected as single-pole power
outputs where the object to be controlled (e.g. a circuit breaker) is electrically
connected in series with the two relay contacts, see the figure below.
doubpole_b
Fig. 5.1.8.1.-2 High-speed single-pole power outputs (HSPO)
!
+
-
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5
+
-
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5

Table of Contents