1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
27
5.1.1.4. Condition monitoring functions
The condition monitoring function blocks are documented on the CD-ROM
“Technical Descriptions of Functions” (refer to “Related documents” on page 9).
5.1.1.5. Communication functions
The RET 54_ transformer terminal provides the IEC_103, Modbus
1
, DNP 3.0
1
, SPA
and LON serial communication protocols.
In a customer-specific transformer terminal configuration, special events can be
generated via an EVENT230 event function. EVENT230 is documented on the CD-
ROM “Technical descriptions of Functions” (refer to “Related documents” on
page 9).
For more information about communication in the RET 54_ transformer terminal,
refer to Section “Serial communication” on page 69.
MMIALAR2 Alarm channel 2, LED indicator
MMIALAR3 Alarm channel 3, LED indicator
MMIALAR4 Alarm channel 4, LED indicator
MMIALAR5 Alarm channel 5, LED indicator
MMIALAR6 Alarm channel 6, LED indicator
MMIALAR7 Alarm channel 7, LED indicator
MMIALAR8 Alarm channel 8, LED indicator
MMIDATA1 MIMIC data monitoring point 1
MMIDATA2 MIMIC data monitoring point 2
MMIDATA3 MIMIC data monitoring point 3
MMIDATA4 MIMIC data monitoring point 4
MMIDATA5 MIMIC data monitoring point 5
Table 5.1.1.3-1 Control functions available for the RET 54_
Function Description
Table 5.1.1.4-1 Conditioning monitoring functions available for the RET 54_
Function Description
CMBWEAR1 Circuit-breaker electric wear 1
CMBWEAR2 Circuit-breaker electric wear 2
CMCU3 Supervision function of the energizing current input circuit
CMGAS1 Gas pressure monitoring
CMGAS3 Three-pole gas pressure monitoring
CMSCHED Scheduled maintenance
CMSPRC1 Spring charging control 1
CMTCS1 Trip circuit supervision 1
CMTCS2 Trip circuit supervision 2
CMTIME1 Operate time counter 1 for the operate time used (e.g. motors)
CMTIME2 Operate time counter 2 for the operate time used (e.g. motors)
CMTRAV1 Breaker travel time 1
CMVO3 Supervision function of the energizing voltage input circuit
1. Requires the use of Bus Communication Module RER 133.