EasyManua.ls Logo

ABB RET 541 - Connector X3.2; X3.2

ABB RET 541
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
69
The following table shows supported parallel communication protocols on the front
and the rear connectors of the RET 54_ transformer terminals.
5.1.13.2. SPA/IEC_103 communication on the rear connector X3.2
The 9-pin D-type subminiature male connector (RS-232 connection) on the rear
panel connects the transformer terminal to the distribution automation system via the
SPA bus or the IEC_103. The fibre-optic interface module type RER 123 is used for
connecting the transformer terminal to the fibre-optic communication bus for SPA
and IEC_103 protocol.
5.1.13.3. DNP 3.0/Modbus communication on the rear connector X3.2
The 9-pin D-type subminiature male connector (RS-232 connection) on the rear
panel connects the transformer terminal to the distribution automation system via the
DNP 3.0 or the Modbus protocol. The RS-485 interface module type RER 133 is
used for connecting the transformer terminal to the RS-485 communication bus of
these protocols.
5.1.13.4. IEC 61850 communication by using SPA-ZC 400 on the rear
connector X3.2
The 9-pin D-type subminiature male connector (RS-232 connection) on the rear
panel connects the transformer terminal to the distribution automation system via the
IEC 61850 protocol. In the IEC 61850 mode, the SPA-ZC 400 Bus Connection
Module is needed.
In the IEC 61850 mode, the baud rate for relay port X3.2 is set to 38400.
Furthermore, the mode includes a limited IEC 61850 GOOSE message support
when available in SPA-ZC 400.
Connectors/Communication parameters
X3.2/Protocol 2 X3.3/Protocol 3 Front connector
SPA (SMS) LON SPA
SPA (SMS) SPA -
IEC_103 LON (SMS) SPA
IEC_103 SPA (SMS) -
IEC_103 - SPA
DNP 3.0 LON (SMS) SPA
DNP 3.0 SPA (SMS) -
DNP 3.0 - SPA
Modbus LON (SMS) SPA
Modbus SPA (SMS) -
Modbus - SPA
IEC 61850 LON (SMS) SPA
IEC 61850 SPA (SMS) -
IEC 61850 - SPA
Profibus LON (SMS) SPA
Profibus SPA (SMS) -
Profibus - SPA
-SPASPA

Table of Contents