40
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
Values to be set for a current transformer:
rated primary current (1...6000 A)
of the primary current transformer
rated secondary current (5 A, 2 A, 1 A, 0.2 A) of the primary current transformer
rated current (5 A, 1 A, 0.2 A) of the current measuring input (= rated current of
the matching transformer of the transformer terminal)
amplitude correction factor (0.9000...1.1000) of the primary current transformer
at rated current
correction parameter for the phase displacement error of the primary current
transformer at rated current (-5.00°...0.00°)
amplitude correction factor of the primary current transformer at a signal level of
1% of the rated current (0.9000...1.1000)
correction parameter for the phase displacement error of the primary current
transformer at a signal level of 1% of the rated current (-10.00°...0.00°)
Values to be set for a voltage transformer:
rated voltage of voltage input (same as the secondary rated voltage of the primary
voltage transformer connected to the voltage input, 100 V, 110 V, 115 V, 120 V)
rated voltage of primary voltage transformer (0.100...440.000 kV)
amplitude correction factor of the primary voltage transformer voltage at rated
voltage (0.9000...1.1000)
correction parameter for the primary transformer phase displacement error at
rated voltage (-2.00°... 2.00°)
The measurement values stated by the manufacturer of the measuring device are
used for calculating the correction parameters and factors according to the following
formulas:
Current transformers
Voltage transformers
Amplitude error at current I
n
(e = error in per cent)
Amplitude correction factor 1
= 1 / (1+ e/100)
Amplitude error at current 0.01 x I
n
(e = error in per cent)
Amplitude correction factor 2
= 1 / (1+ e/100)
Phase displacement error at current I
n
(e = error in degrees)
Phase displacement error 1 = - e
Phase displacement error at current 0.01 x I
n
(e = error in degrees)
Phase displacement error 2 = - e
Amplitude error at voltage U
n
(e = error in per cent)
Amplitude correction factor
= 1 / (1+ e/100)
Phase displacement error at voltage U
n
(e = error in degrees)
Phase displacement error = - e