EasyManua.ls Logo

ABB REU 523 - Page 6

ABB REU 523
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Combined overvoltage and undervoltage
relay
REU 523
1MRS 751123-MBG
6
7DEOH$X[LOLDU\VXSSO\YROWDJH
U
aux
rated Ur =110/120/220/240 V ac
Ur =48/60/110/125/220 V dc
U
aux
variation 80…265 V ac
38…265 V dc
Relay power start-up time, typical 300 ms
Burden of auxiliary supply under
quiescent/operating condition
~ 4 W/~ 10 W
Ripple in the dc auxiliary voltage Max 12% of the dc value
Interruption time in the auxiliary dc voltage without
resetting the relay
< 30 ms at 48 V dc
< 100 ms at 110 V dc
< 500 ms at 220 V dc
7DEOH(QFORVXUHFODVV
Front side IP 54 (flush-mounted)
Rear side, connection terminals IP20
Note! A rear protective cover (accessory part) can be used to protect and shield the rear of the case.
7DEOH'LPHQVLRQV
Width Frame 111.4 mm, box 94.0 mm
Height Frame 265.9 mm (6U), box 249.8 mm
Depth 235 mm (245.1 mm with a protective rear cover,
available as an option)
Enclosure size 1/4 (x 19”)
Weight of the relay ~3.2 kg
7DEOH(QYLURQPHQW DOWHVW V
Specified service temperature range -10...+55 °C
Storage temperature tests -40...+70 °C according to the IEC 60068-2-48
Dry heat test According to the IEC 60068-2-2
Dry cold test According to the IEC 60068-2-1
Damp heat test, cyclic According to the IEC 60068-2-30
7DEOH6WDQGDUGWHVWV
,QVXODWLRQ WHVWV
Dielectric tests According to the IEC 60255-5
Test voltage 2 kV, 50 Hz, 1 min
Impulse voltage test According to the IEC 60255-5
Test voltage 5 kV, unipolar impulses, waveform 1.2/50 µs, source
energy 0.5 J
Insulation resistance measurements According to the IEC 60255-5
Isolation resistance > 100 M, 500 V dc
0HFKDQLFDOWHVWV
Vibration tests (sinusoidal) According to the IEC 60255-21-1, class I
Shock and bump test According to the IEC 60255-21-2, class I
Seismic test According to the IEC 60255-21-3, class 2
7DEOH(OHFWURPDJQHWLFFRPS DWLELOLW\WHVW V
EMC immunity test level requirements consider the demands in the generic standard
EN 50082-2
1 MHz burst disturbance test, class III According to the IEC 60255-22-1
- common mode 2.5 kV
- differential mode 1.0 kV
Electrostatic discharge test, class III According to the IEC 61000-4-2 and
IEC 60255-22-2
- for contact discharge 6 kV

Other manuals for ABB REU 523