*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
&KDSWHU &RQILJXUDWLRQ
90 3BSE 020 923R101
 3RZHUDQG&RROLQJ
Table 3-4 shows the typical power and cooling values that can be used when
designing the S800 I/O.
7DEOH  ,26WD WLRQ3RZHUDQG&RROLQJ7\SLFDO
'HY LFH
9ROW V
0RGX OH%XV
9ROW V
0RGXOH%XV
9ROW V
([WH UQDO
3RZHU
'LV VLSDWLRQ
:DWWV
&RROLQJ
/RDG

%78+
7\SLFDO
0D[LPXP$PELHQW
7HPSHUDWXUH
AI810 70 mA 40 mA - 1.5 5.1 55/40°C (131/104°F)
(2)
AI820 80 mA 70 mA - 1.7 5.8 55/40°C (131/104°F)
(2)
AI830 80 mA 80 mA - 2.2 10 55/40°C (131/104°F)
(2)
AI835 75 mA 50 mA - 1.6 5.4 55/40°C (131/104°F)
(2)
AI890 70 mA - 200 mA 1.5 5.1 55/40°C (131/104°F)
(2)
AO810 70 mA - 200 mA 3.0 10 55/40°C (131/104°F)
(2)
AO820 100 mA 200 mA - 2.8 9.6 55/40°C (131/104°F)
(2)
AO890 70 mA - 200 mA 3.1 10.4 55/40°C (131/104°F)
(2)
DI810 50 mA - - 1.8 6.1 55/40°C (131/104°F)
(2)
DI811 50 mA - - 2.7 9.2 55/40°C (131/104°F)
(2)
DI814 50 mA - - 1.8 6.1 55/40°C (131/104°F)
(2)
DI820 50 mA - - 2.8 9.6 55/40°C (131/104°F)
(2)
DI821 50 mA - - 2.8 9.6 55/40°C (131/104°F)
(2)
DI830 120 mA - - 2.3 7.8 55/40°C (131/104°F)
(2)
DI831 120 mA - - 3.2 10.9 55/40°C (131/104°F)
(2)
DI885 160 mA 91 mA
(3)
91 mA
(3)
3.0 10 55/40°C (131/104°F)
(2)
DI890 50 mA - 50 mA 1.4 5.7 55/40°C (131/104°F)
(2)
DO810 80 mA -
(4)
2.1 7.2 55/40°C (131/104°F)
(2)
DO814 80 mA -
(4)
2.1 7.2 55/40°C (131/104°F)
(2)
DO815 130 mA - 2 A
(5)
4.0 13.6 55/40°C (131/104°F)
(2)

Other manuals for ABB S800 I/O