&DOFXODWLRQRI9GF3RZ HU&RQVXPSWLRQ
Total 24V d.c. power consumption = Σ 24V load ModuleBus + Σ 5V load
ModuleBus*0.3 +
Σ 24V external load.
The calculated 24V ModuleBus load should not exceed 1.3A.
DO820 60 mA 140 mA - 2.9 9.9 55/40°C (131/104°F)
(2)
DO821 60 mA 140 mA - 2.9 9.9 55/40°C (131/104°F)
(2)
DO890 80 mA - 250 mA 4.4 14.9 55/40°C (131/104°F)
(2)
DP820 120 mA -
(4)
2.5 8.5 55/40°C (131/104°F)
CI810 - - 110 mA 2.6 8.9 55°C/(131°F)
CI820 - - 250 mA
(6)
6.0 20 55°C/(131°F)
CI830 - - 110 mA 2.6 8.9 55°C/(131°F)
TB810 100 mA 20 mA - 0.5 1.7 55°C/(131°F)
TB811 100 mA 20 mA - 0.5 1.7 55°C/(131°F)
TB820 - - 100 mA 2.4 8.2 55°C/(131°F)
SD811 - - 11 37 55°C/(131°F)
(7)
SD812 - - 22 75 55°C/(131°F)
(7)
(1) Cooling load is the heat (BTU/H) produced by the equipment that may be required to meet room or enclosure cooling
specifications.
(2) 40°C (104°F) applies to Compact MTUs with I/O modules mounted on a vertical DIN rail.
(3) 24V from ModuleBus (91 mA) or 24V external (91 mA) or 48V external (22 mA).
(4) 500 mA per channel with maximum load per channel.
(5) 2A per channel with maximum load per channel.
(6) CI820 in redundant configuration 2 x 250 mA
(7) Horizontal mounting only.
7DEOH ,26W DWLR Q3RZHUDQG&RROLQJ7\SLFDO &RQWLQXHG