*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHUV*XLGH
6HFWLRQ$ 6'6'3RZHU6XSSO\0RGXOH9GF
3BSE 020 923R101 107
Rated Input Current
230V a.c.
110V a.c.
220V d.c.
0.45A
0.8A
0.32A
0.9A
1.6A
0.65A
Power on surge current 3.5A 7A
Primary power protection Fusable links Fusable links
Output power protection Electronic short-circuit protection Electronic short-circuit protection
Ambient temperature
Transport (max)
Storage (max)
Operating (nominal)
-25
o
C to 70
o
C (-13°F to 158°F)
-25
o
C to 55
o
C (-13°F to 131°F)
5
o
C to 55
o
C (41°F to 131°F)
-25
o
C to 70
o
C (-13°F to 158°F)
-25
o
C to 55
o
C (-13°F to 131°F)
5
o
C to 55
o
C (41°F to 131°F)
Relative humidity 10% - 75% 10% - 75%
Approvals Also meeting the requirements for
a CE mark based upon the Low
Voltage Directive 73/23/EEC;
requirements referring to EN
50178 including EMC capabilities
meeting the EN 50081-2, EN
50082-2.
Also meeting the requirements for
a CE mark based upon the Low
Voltage Directive 73/23/EEC;
requirements referring to EN
50178 including EMC capabilities
meeting the EN 50081-2, EN
50082-2.
Safety classification Class I according to IEC 536;
(earth protected)
Class I according to IEC 536;
(earth protected)
Protection rating IP20 according to IEC 529, (IEC
144)
IP20 according to IEC 529, (IEC
144)
Rated insulation voltage 300V 300V
Dielectric test voltage 2,2kV a.c. 2,2kV a.c.
Width 50 mm (2”) 125 mm (5”)
7DEOH $ 6'6'3RZHU6XSSO\0RGXOH6SHFL ILFDWLR QV&RQWLQXHG
,WHP 6'9DOXH 6'9 DOXH