*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHUV*XLGH
6HFWLRQ 6'DQG6'3RZHU6XSSO\&RQILJXUDWLRQV
3BSE 020 923R101 85
Figure 3-13 shows the connections to redundant CI820 FCIs.
This power supply can be utilized for non-redundant and redundant applications and
does not require additional load-sharing control equipment such as diode voting
units.
)LJXUH &RQQHFWLRQ'LDJUDP VIRU5HGXQGDQW3RZHU6XSSOLHVWR5HGXQGDQW)&,V
L+
L-
SA
SB
+24V
0V
PowOK
SD811/812
CI820
+24V
0V
PowOK
SD811/812
L+
L-
SA
SB
L+
L-
SA
SB
+24V
0V
PowOK
SD811/812
Fuse
or MCB
Optional
Power to
field circuits
via MTUs
CI820 CI820TB815
+24V
0V
PowOK
SD811/812
Circuit
Breaker
Diode
Voting
Unit
SELV