*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
&KDSWHU &RQILJXUDWLRQ
86 3BSE 020 923R101
 3RZHU6XSSO\/RDG&DOFXODWLRQ
$SSURSULDWH+DUGZDUH
Different power supply systems are available for the S800 I/O Station. The number
of power supply units is calculated with respect to actual number of S800 I/O
modules supported by the Station, see Section 3.1.7, Power Supply Requirements
for details.
Normally you don’t have to deal with current consumption calculations, however
there are occasions with special requirements, or designs when detailed information
regarding current consumption is valuable. Please find a description of special
power supply usage under the guidelines below.
*XLGHOLQHV
A summary of the main requirements of the plant supply, from a planning point
of view, is found in Section 2.1, Site Planning.
Auxiliary equipment in the controlled system is normally powered separately
from the S800 I/O power supplies.
If field devices are grounded, be sure to use galvanic isolation.
Heavy current on/off loads are
DOZD\ V
powered separately
It is possible to use the system power supply for transmitters/transducers:
There is idle capacity in the available power supply units
The transducer is grounded directly in the control system chassis
Number of Power Supply Units/Power Consumption
The I/O Station requires 24V d.c. @ 1 amp for the FCI and 12 I/O modules.
Additional power may be required for field devices.
Circuit breakers or a diode voting unit at the power supplies output are required
LI
hot replacement of supplies is required