EMC Section 3 Technical Data and Performance
118 3BSE015969-600 A
Table 18. Immunity IEC/EN 61000-6-2, IEC/EN 61131-2
Immunity IEC/EN 61000-6-2, IEC/EN 61131-2 Continuous...
Test Severity
Generic
standards
Radiated RF field 80MHz – 1.0GHz, 10 V/m
1.4GHz – 2.0GHz, 3 V/m
2.0GHz – 2.7GHz, 1 V/m
EN/IEC 61000-6-2,
EN/IEC 61131-2
Conducted RF field 0.15MHz-80MHz, 10V EN/IEC 61000-6-2,
EN/IEC 61131-2
Table 19. Transients Immunity
Transients immunity
Electrostatic
discharge
4 kV contact discharge
8 kV air discharge
IEC 61000-6-2,
IEC 61131-2
Electrical fast
transient/Burst
2 kV, AC/DC, process I/O AC
1 kV, Process I/O DC, analog I/O and
com
IEC 61000-6-2,
IEC 61131-2
Surge 2 kV common mode, AC/DC power ports,
process I/O AC
1 kV differential mode, Process I/O DC,
analog I/O and com
IEC 61000-6-2,
IEC 61131-2