Section 3 Technical Data and Performance EMC
3BSE015969-600 A 117
EMC
Table 16. Radiated Radio Frequency Emission IEC/EN 61000-6-4 (Class A),
IEC/EN 61131-2
Radiated Radio Frequency Emission IEC/EN 61000-6-4 (Class A),
IEC/EN 61131-2
Test Limits
Generic
st
andards
30 MHz -230 MHz 40 dB (µV/m) quasi peak measured at
10
m
EN/IEC 61000-6-4,
EN/IEC 61131-2
230 MHz - 1000
MH
z
47 dB (µV/m) quasi peak measured at
10m
Table 17. Conducted Radio Frequency Emission, AC mains port IEC 61000-6-4
(Class A), IEC/EN 61131-2
Conducted Radio Frequency Emission, AC mains port IEC 61000-6-4 (Class
A), IEC/EN 61131-2
Test Limits
Generic
standards
0,15 MHz -0,50
MHz
79 dB (µV/m) quasi peak
66 dB (µV/m) average
EN/IEC 61000-6-4,
EN/IEC 61131-2
0,50 MHz - 30 MHz 73 dB (µV) quasi peak
60 dB (µV/m) average