PROFIBUS CI840 Section 3 Technical Data and Performance
134 3BSE015969-600 A
In order to find out if a given configuration of analog and digital modules can be
used, the following method should be used:
Fill in number of modules in Table 27.
Calculate the sum in the three columns:
Sum User Parameters
Sum Input Bytes
Sum Output Bytes
Calculate the three total sums for:
ParamSize
–InSize
OutSize.
Check that:
ParamSize is less than or equal to 221 (220 if HCIR is used)
InSize is less than or equal to 239 in normal mode, 199 in Extended HART
mode
OutSize is less than or equal to 112 in normal mode, 90 in Extended
HART mode
If any of these three values is too high then the configuration can not be used.