12. Unidad de protección PR111/LI - LSI - LSIG
12.1 Generalidades
La unidad SACE PR111/P realiza las siguiente funciones de protección:
L – protección contra sobrecarga a tiempo largo inverso
S – protección contra cortocircuito a tiempo corto
I – protección contra cortocircuito instantáneo
G – protección contra defecto a tierra
Iinst – protección rápida contra cortocircuito instantáneo
Las unidades SACE PR111 disponibles para el usuario son:
PR111/L+I+Iinst
12. PR111/LI - LSI - LSIG protection unit
12.1 General
The SACE PR111/P unit carries out the following protection functions:
L – protection against overload with inverse long time-delay
S – protection against short-time short-circuit
I – protection against instantaneous short-circuit
G – protection against earth fault
Iinst – rapid protection against instantaneous short-circuit
The SACE PR111 units available to the user are:
In=
I
TEST
L
I
1
=
t
1
x
I
n
ABCD
0.4
0.5 0.6 0.7 0.8 0.9 0.95 1
I
3
=
x
I
n
1.5
24681012
OFF
I
=
6
I
1
Nr.=
15 Vdc
+
InN = In/2
L
I
t
t1
I
I
3
I
1
3s
6s
12s
18s
SACE PR111/P
SI
TEST
L
I1=
t1
OFF
12346810
ABCD
x In
ABCD
0.4
0.5 0.6 0.7 0.8 0.9 0.95 1
I2=
x In
I3=
x In
1.5
24681012
OFF
I=6I1
I=8In
I>I2
t2
Nr.=
15 Vdc
+
InN = In/2
L
S
I
t
t1
t2
InI3I2I1
In=
0.05s
0.10s
0.25s
0.5s
3s
6s
12s
18s
SACE PR111
SI G
TEST
L
I1=
t1
OFF
12346810
ABCD
x In
ABCD ABCD
0.4
0.5 0.6 0.7 0.8 0.9 0.95 1
I2=
x In
I3=
x In
I4=
x In
1.5
24681012
OFF
0.2 0.3 0.4 0.6 0.8 0.9 1
OFF
I=6I1
I=8In
I>I2
t2 t4
Nr.=
15 Vdc
+
InN = In/2
In=
t
t4
I
I4
SACE PR111
0.1s
0.2s
0.4s
0.8s
0.05s
0.10s
0.25s
0.5s
3s
6s
12s
18s
The protections can be made either in three-phase or three-phase with
neutral mode, depending on the type of circuit-breaker used (three-pole,
four-pole or three-pole with external neutral).
The unit is self-powered and ensures correct operation of the protection
functions when there is a current higher than or equal to 18% of the rated
phase current transformer value (CT).
The protection release assembly consists of the following:
– 3 or 4 current transformers (CT)
– SACE PR111 protection unit
– an opening solenoid (OS) of the overcurrent release which acts directly
on the circuit-breaker operating mechanism.
Las protecciones se pueden efectuar de manera trifásica o trifásica con
neutro en función del tipo de interruptor utilizado (tripolar, tetrapolar o
tripolar con neutro exterior).
La unidad está autoalimentada y garantiza el funcionamiento correcto de
las funciones de protección en presencia de una corriente mayor o igual
al 18% del valor nominal del transformador amperimétrico de fase (TA).
El grupo relé de protección está formado por:
– 3 o 4 transformadores de corriente (TA)
– unidad de protección SACE PR111
– un solenoide de apertura (SA) del relé de sobreintensidad que actúa
directamente en el mando del interruptor.
PR111/L+S+I+G+Iinst
PR111/L+S+I+Iinst
Fig. 47