EasyManua.ls Logo

ABB SACE Emax - Page 56

ABB SACE Emax
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N° Doc.
Doc. No.
Mod.
Rev.
M4379
SACE Emax
601933/003
Aparato
Apparatus
Escala
Scale
N° Pag.
Sh. No.
54/100
I1 = 0.5 x In t1 = Curva /
Curve
“C”
I1
Valor teórico I/In /
Theoretical /In value
= 925 / 2000 = 0.4625
El valor práctico que se debe programar es I1 /
The practical value to set is
I1 = 0.5
Is = (5 x I) / (I1 x In) = (5 x 925) / (0.5 x 2000 ) = 4.625
Curva /
Curve
A: I²t = 6I1 x 6I1 x 3 = 108 I1²
Curva /
Curve
B: I²t = 6I1 x 6I1 x 6 = 216I1²
Curva /
Curve
C: I²t = 6I1 x 6I1 x 12 = 432 I1²
Curva /
Curve
D: I²t = 6I1 x 6I1 x 18 = 648I1²
Curva/
Curve
a) Se calcula la relación entre la corriente de circulación y la corriente
nominal del TA que define la fracción de In teórica:
b) Se calcula (Is) la relación entre la corriente de sobrecarga y el valor de
corriente I1 programado que define el múltiplo de I1:
c) Sucesivamente, es necesario buscar la curva dentro de la cual, con
una sobrecarga de 4.625 x I1, el tiempo de actuación no supere los
25s.
Utilizando la fórmula I²t = Cost se calculan los valores de las
constantes de las curvas A, B, C y D (véase párrafo 12.8):
a) The relationship between the circulating current and the rated current
of the CT is calculated, which defines the fraction of theoretical:
b) The relationship (Is) between the overload current and the current
value I1 set, which defines the multiple of I1:
c) It is now necessary to look for the curve within which, with an overload
of 4.625 x I1, the trip time is not longer than 25s.
Using the I²t relationship = Const, we calculate the values of the
constants of the curves A, B, C and D (see para. 12.8):
Now we calculate the real trip time according to the selected curve:
Luego, se calcula el tiempo real de actuación en función de la curva
seleccionada:
De esta manera se deduce que la curva que se debe programar es la
“C “ya que es la que mejor cumple con los requisitos. La programación
será la siguiente:
The curve to be set is definitely the “C” one as it best fulfils our
requirements. The protection setting will therefore be as follows:
Curva /
Curve
A: t1 = 108 I1² / (IsI1 x IsI1 ) = 108 /(4.625 x 4.625) = 5.0 s
Curva /
Curve
B: t1 = 216I1² / (IsI1 x IsI1 ) = 216 /(4.625 x 4.625) = 10.1s
Curva /
Curve
C: t1 = 432 I1² / (IsI1 x IsI1 ) = 432/(4.625 x 4.625) = 20.2s
Curva /
Curve
D: t1 = 648I1² / (IsI1 x IsI1 ) = 648/(4.625 x 4.625) = 30.3s
Curva A tiempo de actuación 3s a 6 x In
Curve A
trip time 3s at 6 x I1
Curva B tiempo de actuación 6s a 6 x I1
Curve B
trip time 6s at 6 x I1
Curva C tiempo de actuación 12s a 6 x I1
Curve C
trip time 12s at 6 x I1
Curva D tiempo de actuación 18s a 6 x I1
Curve D
trip time 18s at 6 x I1
Curva/
Curve
A
Curva/
Curve
B
Curva/
Curve
C
Curva/
Curve
D
12.3.1.2 Selection of the trip curve (t1)
4 different trip curves can be selected by using the dip-switches indicated
in fig. 48 ref. R.
These curves are defined by the function I²t = defined Const (*) of the
values:
The trip time tolerance is ± 10% up to 2 x In and ± 20% over 2 x In.
(*) The minimum value of this trip is 750 ms regardless of the type of curve
set (self-protection).
The table below shows the possible settings:
La tolerancia en los tiempos de actuación es ± 10% hasta 2 x In y ± 20%
para más de 2 x In.
(*) El valor mínimo de dicha actuación es de 750ms independiente del
tipo de curva programada (autoprotección).
En la siguiente tabla se indican las programaciones posibles:
12.3.1.2 Selección de la curva de actuación (t1)
Se pueden seleccionar 4 curvas de actuación diferentes configurando los
dip-switch indicados en la fig. 48 ref. R .
Dichas curvas se definen mediante la función I²t = Cost (*) determinada
por los valores:
12.3.1.3. Ejemplo de programación
A continuación se ilustra un ejemplo de programación de la protección
a tiempo largo inverso (L).
Se desea efectuar una protección con las siguientes características:
Un interruptor SACE Emax con TA de 2000A y una corriente nominal
de circulación de 925A.
Se desea proteger la carga de esta manera:
en un tiempo de 25s con una sobrecarga 5 veces superior a la corriente
de circulación.
12.3.1.3 Example of setting
An example of inverse long time-delay (L) setting of the protection is
given.
A protection with the following characteristics is to be made:
A SACE Emax circuit-breaker mounts 2000A CTs and the circulating
service current is 925A.
The load is to be protected as follows:
within a time of 25s with an overload 5 times the circulating current

Other manuals for ABB SACE Emax

Related product manuals