EasyManua.ls Logo

ABB SACO 16D1 - Page 41

ABB SACO 16D1
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
Serial communication port
Protocol SPA bus
Interface RS 485
Data interchange speed, selectable 9600 Baud
4800 Baud
2400 Baud
1200 Baud
300 Baud
Bus connection modules SPA-ZC 17 or SPA-ZC 21
Auxiliary power supply
Internal power unit for any supply voltage 80. . .265 V dc or ac
or 18...80 V dc
Power demand from auxiliary source, min. /max. values 10 W/15 W
Test voltages
Test voltages applied to the following points:
- alarm- and acknowledge/reset inputs to the frame
- output relay contacts to the frame
- auxiliary supply circuits to the frame
- inputs, outputs and supply circuits between themselves
Dielectric test voltage as per IEC 255-5 2 kV, 50 Hz, 1 min.
and SS 436 15 03
Impulse test voltage as per IEC 255-5 5 kV, 1.2/50 ps, 0.5 J
and SS 436 15 03
High-frequency interference test voltage as per 2.5 kV, 1 MHz
IEC 255-6 and SS 436 15 03
Environmental conditions
Service temperature range -10. . . +55°C
Storage temperature range -40. . . +70°C
Heat and damp as per I EC 68-2-3 < 95 % max. 56 d/y at +40 C
Degree of protection by enclosure IP 54
Weight 3.1 kg

Table of Contents