EasyManua.ls Logo

ABB SC - Page 6

ABB SC
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.L. 41-766.1N SC, SC-1, SV and SV-1 Relay
6
CHARACTERISTICS OF TYPES SC AND SC-1 RELAYS
Type Frequency
Range of
Adjustment
Amps.
Max. Amps.
Continuous
Watts at
5 Amps.
60 Cycles
V.A. at
5 Amps.
60 Cycles
Dropout
Ratio-AC
Dropout
Ratio-DC
SC
SC
SC
SC
SC
SC
SC
SC
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
.5-2
1-4
2-8
4-16
10-40
20-80
40-160
4-100
1.5
3
6
12
25
40
40
10-15-20
99
28
6.9
1.5
.24
.07
.03
1.7-0.6-0.18
225
65
19
5
.7
.16
.05
5-1-0.2
85-98%
85-98%
85-98%
85-98%
85-98%
85-98%
85-98%
85-98%
65-80%
65-80%
65-80%
65-80%
65-80%
65-80%
65-80%
65-80%
SC-1
SC-1
SC-1
SC-1
SC-1
SC-1
SC-1
SC-1
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
DC, 25 to 60 Hz
.5-2
1-4
2-8
4-16
10-40
20-80
40-160
4-100
*
1.5
3
6
12
25
40
40
10-15-20
100
24
6
1.5
.25
.07
.03
1.7-0.6-0.18
210
60
16
5
.65
.16
.05
5-1-0.2
35-60%
35-60%
35-60%
35-60%
35-60%
35-60%
35-60%
35-60%
25-40%
25-40%
25-40%
25-40%
25-40%
25-40%
25-40%
25-40%
* Coil has taps on which minimum pickups are 10 and 30 amperes.