ABB SPAJ 140 C - SPCJ 4 D29 Unit Settings; Overcurrent and Earth-fault Stage Configuration

ABB SPAJ 140 C
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Overcurrent unit of SPCJ 4D29
Low-set overcurrent stage I> *
Start current **
- at definite time characteristic 0.5...5.0 x I
n
- at inverse time characteristic *** 0.5…2.5 x I
n
Time/current characteristic
- definite time characteristic
- operate time t> 0.05...300 s
- inverse definite minimum time (IDMT)
characteristic as per IEC 60255-3 and BS 142 Extremely inverse
Very inverse
Normal inverse
Long-time inverse
- special type inverse characteristic RI-type inverse
RXIDG-type inverse
- time multiplier k 0.05...1.0
High-set overcurrent stage I>> *
Start current 0.5...40 x I
n
and , infinite
Operate time t>> 0.04...300 s
Earth-fault unit of SPCJ 4D29
Low-set earth-fault stage I
0
> *
Start current 0.1...0.8 x I
n
Time/current characteristic
- definite time characteristic
- operate time t
0
> 0.05...300 s
- inverse definite minimum time (IDMT)
characteristic as per IEC 60255-3 and BS 142 Extremely inverse
Very inverse
Normal inverse
Long-time inverse
- special type inverse characteristic RI-type inverse
RXIDG-type inverse
- time multiplier k
0
0.05...1.0
High-set earth-fault stage I
0
>> *
Start current 0.1...10.0 x I
n
and , infinite
Operate time t
0
>> 0.05... 300 s
* Note!
The operation of the low-set stage based on
inverse time characteristic will be blocked by
starting of the high-set stage. Then the operate
time of the overcurrent unit is determined by
the set operate time of the high-set stage at heavy
fault currents. In order to obtain a trip signal,
the high-set stage must be routed to a trip output
relay.
** Note!
If the set start current exceeds 2.5 x I
n
, the
maximum continuous carry of the energizing
inputs (4 x I
n
) must be noted.
*** CAUTION!
Never use start current settings above 2.5 x I
n
at
inverse time operation although allowed by the
relay.