30
Data Code Data Values
direction
Memorized I> start signal O21 R 0 = signal not active
1 = signal active
Memorized I> operate signal O22 R 0 = signal not active
1 = signal active
Memorized I>> start signal O23 R 0 = signal not active
1 = signal active
Memorized I>> operate signal O24 R 0 = signal not active
1 = signal active
Memorized I
0
> start signal O25 R 0 = signal not active
1 = signal active
Memorized I
0
> operate signal O26 R 0 = signal not active
1 = signal active
Memorized I
0
>> start signal O27 R 0 = signal not active
1 = signal active
Memorized I
0
>> operate signal O28 R 0 = signal not active
1 = signal active
Memorized output signal TS1 O29 R 0 = signal not active
1 = signal active
Memorized output signal SS1 O30 R 0 = signal not active
1 = signal active
Memorized output signal SS2 O31 R 0 = signal not active
1 = signal active
Memorized output signal SS3 O32 R 0 = signal not active
1 = signal active
Memorized output signal TS2 O33 R 0 = signal not active
1 = signal active
PRESENT SETTING VALUES
Present start value for stage I> S1 R 0.5...5.0 x I
n
Present operate time or time S2 R 0.05...300 s
multiplier for stage I> 0.05…1.0
Present start value for stage I>> S3 R 0.5...40 x I
n
999 = not in use (∞)
Present operate time for stage I>> S4 R 0.04...300 s
Present start value for stage I
0
> S5 R 0.1...0.8 x I
n
Present operate time or time S6 R 0.05...300 s
multiplier for stage I
0
> 0.05…1.0
Present start value for stage I
0
>> S7 R 0.1...10.0 x I
n
999 = not in use (∞)
Present operate time for stage I
0
>> S8 R 0.05...300 s
Present checksum of S9 R 0...255
switchgroup SGF1
Present checksum of S10 R 0...255
switchgroup SGF2
Present checksum of S11 R 0...255
switchgroup SGB
Present checksum of S12 R 0...255
switchgroup SGR1
Present checksum of S13 R 0...255
switchgroup SGR2
Present checksum of S14 R 0...255
switchgroup SGR3