COMBINED OVERCURRENT AND EARTH-FAULT RELAY MODULE SPCJ 4D24
Current measuring module.......................................................................SPCJ
Number of measurands.......................................................................................4
Type designation....................................................................................................D24
C o n t e n t s Page
Characteristics 1
Description of function 2
Block diagram 4
Front panel 5
Operation indicators 5
Settings 6
Programming switches 7
Measured data 12
Recorded information 12
Main menus and submenus of settings and registers 14
Time/current characteristics 16
Technical data 22
Serial communication 23
Fault codes 31
C h a r a c t e r i s t i c s
The combined overcurrent and earth-fault module includes:
- A low-set overcurrent stage I> with a definite time and six inverse time
modes of operation
- A high-set overcurrent stage I>> with a setting range of 0.5...40 x I
n
. The
operation of the high-set overcurrent stage can be set out of function
- A low-set neutral overcurrent stage I
o
> with a setting range of
1.0...25.0 % I
n
and definite time mode of operation
- A high-set neutral overcurrent stage I
o
>> with a setting range of
2.0...200 % I
n
. The operation of the high-set neutral over current stage
can be set out of function
- Digital display of measured and set values and sets of data recorded
at the moment when faults occurs
- All settings may be keyed in using the push-buttons of the front panel
or they may be set using a personal computer
- Continuous self-supervision including both hardware and software. At
a permanent fault the alarm output relay operates and the other outputs
are blocked.
KORVAA-ERS
TTER-SUPERSEDES
KORVATTU-ERSATT MED-SUPERSEDED BY
JAKELU
FÖRDELNING
DISTRIBUTION
HAKEMISTO
REGISTER
FILE
LEHTI
BLAD
SHEET
NIMITYS-BEN
MNING-NAME
TARKASTANUT
GRANSKAD
CHECKED
ABB Relays
HYV
KSYNYT
GODKÄND
APPROVED
TEKI-SKRIVEN AV-WRITTEN BY
LAJI - TYP - TYPE
Overcurrent and earth-fault relay module SPCJ 4D24
1993 - 03 - 30 H Sundell 34 SPCJ 9 EN 1 E
RESET
STEP
PROGRAM
SGR
IL1 IL2 IL3 Io
IRF
SGB
I»[In]
Io»[%In]
t»[s]
to»[s]
TRIP
SPCJ 4D 24
SGF
I>[In]
Io>[%In]
t>[s]
k
to>[s]
3I>