Data to be transferred over the serial bus
In addition to the spontaneous data transfer the SPA bus allows reading of all input data (I-data) of the
module, setting values (S-values), information recorded in the memory (V-data), and some other data.
Further, part of the data can be altered by commands given over the SPA bus. All the data are available
in channel 0.
R = data to be read from the unit
W = data to be written to the unit
(P) = writing enabled by a password
Data Code Data Values
direction
INPUTS
Measured current on phase L1 I1 R 0...63 x In
Measured current on phase L2 I2 R 0...63 x In
Measured current on phase L3 I3 R 0...63 x In
Measured neutral current I4 R 0...210 % In
Blocking or control signal I5 R 0 = no blocking
1 = external blocking or control
signal active
OUTPUTS
Starting of stage I> O1 R 0 = I> stage not started
1 = I> stage started
Tripping of stage I> O2 R 0 = I> stage not tripped
1 = I> stage tripped
Starting of stage I>> O3 R 0 = I>> stage not started
1 = I>> stage started
Tripping of stage I>> O4 R 0 = I>> stage not tripped
1 = I>> stage tripped
Starting of stage I
o
> O5 R 0 = I
o
> stage not started
1 = I
o
> stage started
Tripping of stage I
o
> O6 R 0 = I
o
> stage not tripped
1 = I
o
> stage tripped
Starting of stage I
o
>> O7 R 0 = I
o
>> stage not started
1 = I
o
>> stage started
Tripping of stage I
o
>> O8 R 0 = I
o
>> stage not tripped
1 = I
o
>> stage tripped
Signal START1 TS1 O9 R, W (P) 0 = signal not active
1 = signal active
Signal START2 SS1 O10 R, W (P) 0 = signal not active
1 = signal active
Signal ALARM1 SS2 O11 R, W (P) 0 = signal not active
1 = signal active