Event codes of the combined overcurrent and earth-fault relay module SPCJ 4D24:
Code/Event Number repre- Default value
senting the of the factor
event
E1 Starting of stage I> 1 1
E2 Starting of stage I> reset 2 0
E3 Tripping of stage I> 4 1
E4 Tripping of stage I> reset 8 0
E5 Starting of I>> stage 16 1
E6 Starting of I>> stage reset 32 0
E7 Tripping of stage I>> 64 1
E8 Tripping of stage I>> reset 128 0
Default checksum for mask V155 85
E9 Starting of stage I
o
>11
E10 Starting of stage I
o
> reset 2 0
E11 Tripping of stage I
o
>41
E12 Tripping of stage I
o
> reset 8 0
E13 Starting of I
o
>> stage 16 1
E14 Starting of I
o
>>stage reset 32 0
E15 Tripping of stage I
o
>> 64 1
E16 Tripping of stage I
o
>> reset 128 0
Default checksum for mask V156 85
E17 Output signal TS1 activated 1 0
E18 Output signal TS1 reset 2 0
E19 Output signal SS1 activated 4 0
E20 Output signal SS1 reset 8 0
E21 Output signal SS2 activated 16 0
E22 Output signal SS2 reset 32 0
E23 Output signal SS3 activated 64 0
E24 Output signal SS3 reset 128 0
E25 Output signal TS2 activated 256 1
E26 Output signal TS2 reset 512 1
Default checksum for mask V157 768
E50 Restarting * -
E51 Overflow of event register * -
E52 Temporary interruption in data communication * -
E53 No response from the module over the data communication * -
E54 The module responds again over the data communication * -
0 not included in the event reporting * no code number
1 included in the event reporting - cannot be programmed
Note ! The event codes E52...E54 are only generated by the data communicator unit (SACO 100M, SRIO
1000M, etc.)