30
PAINOS
PAINOS
Data comm. address of the module V200 R, W 1...254
Data transfer rate V201 R, W 4,8 or 9,6 Bd
Programme version symbol V205 R 042 _
Event register reading L R time, channel number
and event code
Re-reading of event register B R time, channel number
and event code
Type designation of the module F R SPCJ 4D24
Reading of module status data C R 0 = normal state
1 = module been subject
to automatic reset
2 = overflow of event regist.
3 = events 1 and 2
together
Resetting of module state data C W 0 = resetting
Time reading and setting T R, W 00.000...59.999 s
The event register can be read by L-command only once. Should a fault occur e.g. in the data transfer, the
contents of the event register may be re-read by means of the L-command using the B-command. When
required, the B-command can be repeated. Generally, the control data communicator SACO 100M reads the
event data and forwards them to the output device continuously. Under normal conditions the event register
of the module is empty. In the same way the data communicator resets abnormal status data, so this data
is normally a zero.
The setting values S1...S14 are the setting values used by the protection functions. These values are set
either as the main settings and switchgroup checksums S21...S34 or as the corresponding second settings
S41...S54. All the settings can be read or written. A condition for writing is that remote set password has been
opened.
When changing settings, the relay unit will check that the variable values are within the ranges specified in
the technical data of the module. If a value beyond the limits is given to the unit, either manually or by remote
setting, the unit will not perform the store operation but will keep the previous setting.