EasyManua.ls Logo

ABB SPAJ 141 C - Control Parameters

ABB SPAJ 141 C
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
PAINOS
PAINOS
C
Number of startings of stage I>> V3 R 0...255
Number of startings of stage I
o
> V4 R 0...255
Number of startings of stage I
o
>> V5 R 0...255
Phase conditions during trip V6 R 1 = I
L3
>, 2 = I
L2
>,
4 = I
L1
>, 8 = I
o
>
16 = I
L3
>>, 32 = I
L2
>>
64 = I
L1
>>, 128 = I
o
>>
Operation indicator V7 R 0...9
Highest maximum demand current
15 minute value V8 R 0…2.55 x I
n
CONTROL PARAMETERS
Resetting of output relays V101 W 1 = output relays and all at
self-holding information from the display are
reset
Resetting of output relays V102 W 1 = output relays and
and recorded data registers are reset
Remote control of settings V150 R, W 0 = main settings activated
1 = second settings activated,
see section "Description of
function"
Event mask word for overcurrent events V155 R, W 0...255, see section "Event
codes"
Event mask word for earth-fault events V156 R, W 0...255, see section "Event
codes"
Event mask word for output signal events V157 R, W 0...1023, see section "Event
codes"
Opening of password for remote settings V160 W 1...999
Changing or closing of password for
remote settings V161 W (P) 0...999
Activating of self-supervision output V165 W 1 = self-supervision output
is activated and IRF
LED turned on
0 = normal mode
LED test V166 W (P) 0...20
Factory final test V167 W (P) 1 = display segment test
2 = format EEPROM with a
power reset for a fault code [53]
Internal error code V 169 R 0...255