28
PAINOS
PAINOS
SECOND SETTING VALUES
Starting value for I> stage, second setting S41 R, W (P) 0.5...5.0 x In
Operating time for I> stage, second setting S42 R, W (P) 0.05...300 s
Starting value for I>> stage, second setting S43 R, W (P) 0.5...40.0 x In
Operating time for I>> stage, second setting S44 R, W (P) 0.04...300 s
Starting value for I
o
> stage, second setting S45 R, W (P) 1.0...25.0 % In
Operating time for I
o
> stage, second setting S46 R, W (P) 0.05...300 s
Starting value for I
o
>> stage, second setting S47 R, W (P) 2...200 % In
Operating time for I
o
>> stage, second setting S48 R, W (P) 0.05...300 s
Checksum of group SGF1, second setting S49 R, W (P) 0...255
Checksum of group SGF2, second setting S50 R, W (P) 0...255
Checksum of group SGB, second setting S51 R, W (P) 0...255
Checksum of group SGR1, second setting S52 R, W (P) 0...255
Checksum of group SGR2, second setting S53 R, W (P) 0...255
Checksum of group SGR3, second setting S54 R, W (P) 0...255
Operation time for circuit breaker failure prot. S61 R, W (P) 0.1...1.0 s
RECORDED AND MEMORIZED PARAMETERS
Current in phase L1 at starting or tripping V11...V51 R 0...63 x In
Current in phase L2 at starting or tripping V12...V52 R 0...63 x In
Current in phase L3 at starting or tripping V13...V53 R 0...63 x In
Netral current I
o
at starting or tripping V14...V54 R 0...210 % In
Duration of the latest starting
situation of stage I> V15...V55 R 0...100%
Duration of the latest starting
situation of stage I>> V16...V56 R 0...100%
Duration of the latest starting
situation of stage I
o
>V17...V57 R 0...100%
Duration of the latest starting
situation of stage I
o
>> V18...V58 R 0...100%
Maximum demand current for 15 min. V1 R 0...2.5 x In
Number of startings of stage I> V2 R 0...255