EasyManua.ls Logo

ABB SPAU 140 C - Dimensions and Instructions for Mounting

ABB SPAU 140 C
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Dimensions and
instructions for
mounting
The basic model of the protection relay case is
designed for flush-mounting. When required,
the mounting depth of the case can be reduced
by means of raising frames: type SPA-ZX 111
reduces the depth by 40 mm, type SPA-ZX 112
by 80 mm and type SPA-ZX 113 by 120 mm.
The type designation of the case for surface
mounting is SPA-ZC 117.
Raising frame
SPA-ZX 111
SPA-ZX 112
SPA-ZX 113
176
136
96
74
114
154
ab
a
b
Panel cut-out
129 ±1
139 ±1
142
162
136
30
34
250
186
216
Fig. 7. Dimension and mounting drawings for synchro-check relay SPAU 140 C.
The relay case is made of anodized profile alu-
minium and finished in beige.
The rubber gasket fitted to the mounting collar
provides an IP 54 degree of protection by en-
closure between the relay case and the mount-
ing base.
The hinged cover of the case is made of trans-
parent, UV-stabilized polycarbonate polymer
and provided with a sealable locking screw. The
rubber gasket of the cover provides an IP 54
degree of protection between the case and the
cover.
The required input and output wires are con-
nected to the screw terminals on the rear panel.
Each terminal screw is dimensioned for one wire
of maximum 6 mm
2
or two wires of maximum
2.5 mm
2
. Part of the control inputs is located
in the detachable six-pole terminal block. The
9-pole D-type connector is intended for serial
communication.

Related product manuals