15
Function selector
switches
Additional functions required by individual
applications are selected by means of switch-
groups SGF, SGB and SGR indicated on the
front panel. The numbering of the switches, i.e.,
1...8, and the switch positions 0 and 1, are in-
dicated when the switches are set. Under nor-
mal service only the checksums are shown on
the display. The switchgroups SGF, SGB and
SGR are software-based and thus not to be
found in the hardware of the relay module.
Functional switch-
group SGF
Switch Function Factory
defaults
SGF/1 Selection of energizing direction for stage 1 in the voltage-check function. 1
SGF/2 1
SGF/1 SGF/2 Energizing direction
0 0 Both "de-energized" or U1U3 or U1U3
10U1U3
01U1U3
11U1U3 or U1U3
SGF/3 Selection of synchro-check function of stage 1. 0
When SGF/3=1, the synchro-check function is enabled.
When SGF/3=0, the synchro-check function is disabled.
SGF/4 Selection of voltage-check function of stage 1. 0
When SGF/4=1, the voltage-check function is enabled.
When SGF/4=0, the voltage-check function is disabled.
SGF/5 Selection of energizing direction for stage 2 in the voltage-check function. 1
SGF/6 1
SGF/5 SGF/6 Energizing direction
0 0 Both "de-energized" or U2U3 or U2U3
10U2U3
01U2U3
11U2U3 or U2U3
SGF/7 Selection of synchro-check function of stage 2. 0
When SGF/7=1, the synchro-check function is enabled.
When SGF/7=0, the synchro-check function is disabled.
SGF/8 Selection of voltage check function of stage 2. 0
When SGF/8=1, the voltage-check function is enabled.
When SGF/8=0, the voltage-check function is disabled.
Checksum for factory setting 51