17
Output relay switch-
group SGR for alarm
signals
The alarms required in command mode opera-
tion are selected by means of switchgroup SGR.
All alarm signals are delivered to the common
output relay ALARM.
Switch Function Factory
defaults
SGR/1 When SGR/1=1, the alarm signal NC13 of stage 1 for a failed CB closing 0
is delivered to the output relay ALARM and the corresponding operation
figure is indicated on the display.
When SGR/1=0, the alarm signal NC13 is blocked.
SGR/2 Switch is not in use. The switch should be in position 0. 0
SGR/3 When SGR/3=1, the alarm signal CSF13 of stage 1 for too long a 0
command signal CS13 is delivered to the output relay ALARM and
the corresponding operation figure is indicated on the display.
When SGR/3=0, the alarm signal CSF13 is blocked.
SGR/4 Switch is not in use. The switch should be in position 0. 0
SGR/5 When SGR/5=1, the alarm signal NC23 of stage 2 for a failed CB closing 0
is delivered to the output relay ALARM and the corresponding
operation figure is indicated on the display.
When SGR/5=0, the alarm signal NC23 is blocked.
SGR/6 Switch is not in use. The switch should be in position 0. 0
SGR/7 When SGR/7=1, the alarm signal CSF23 of stage 2 for excessive duration 0
of the command signal CS23 is delivered to the output relay ALARM and
the corresponding operation figure is indicated on the display.
When SGR/7=0, the alarm signal CSF23 is blocked.
SGR/8 Switch is not in use. The switch should be in position 0. 0
Checksum for factory setting 0