26
Code Event Weighting Default
coefficient setting
E7 Starting of SC23 1 0
E8 Starting of SC23 reset 2 0
E9 Closing permission/command of SC23 4 1
E10 Starting of VC23 8 0
E11 Starting of VC23 reset 16 0
E12 Closing permission/command of VC23 32 1
Default value of event mask V156 36
E13 Input signal BS13 activated 1 0
E14 Input signal BS13 reset 2 0
E15 Input signal CS13 activated 4 0
E16 Input signal CS13 reset 8 0
E17 Input signal BS23 activated 16 0
E18 Input signal BS23 reset 32 0
E19 Input signal CS23 activated 64 0
E20 Input signal CS23 reset 128 0
Default value of event mask V158 0
E21 Output signal CB13 activated 1 1
E22 Output signal CB13 reset 2 1
E23 Output signal CB23 activated 4 1
E24 Output signal CB23 reset 8 1
E25 Output signal ALARM activated 16 1
E26 Output signal ALARM reset 32 1
Default value of event mask V157 63
E50 Restart of microprocessor * -
E51 Overflow of event register * -
E52 Temporary interruption in data communication * -
E53 No response from the relay module over the data * -
communication bus
E54 The relay module responds again over the data * -
communication bus
Explanations:
0 not included in event reporting
1 included in event reporting
* no code number, always included in event reporting
- cannot be set
SC13 synchro-check function of stage 1
SC23 synchro-check function of stage 2
VC13 voltage-check function of stage 1
VC23 voltage-check function of stage 2