28
Data Code Data Value
direction
Setting values
General setting values for reading:
Upper threshold voltage U
max
S1 R 0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S2 R 0.10 ... 0.80 x U
n
Voltage difference value U S3 R 0.02 ... 0.40 x U
n
Phase angle difference value ∆ϕ S4 R 5 ... 50°
Frequency difference value f S5 R 0.02 ... 0.50 Hz
Operate time (dead time) for t
VC
S6 R 0.10 ... 20 s
Check time in command mode operation, t
check
S7 R 0.05 ... 300 s
Closing signal length t
pulse
S8 R 0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker, t
CB13
(stage 1) S9 R 0.05 ... 0.25 s
Operate time of circuit breaker, t
CB23
(stage 2) S10 R 0.05 ... 0.25 s
Checksum of switchgroup SGF S11 R 0 ... 255
Checksum of switchgroup SGB S12 R 0 ... 255
Checksum of switchgroup SGR S13 R 0 ... 255
Main settings
Upper threshold voltage U
max
S21 R,W,(P) 0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S22 R,W,(P) 0.10 ... 0.80 x U
n
Voltage difference U S23 R,W,(P) 0.02 ... 0.40 x U
n
Phase angle difference ∆ϕ S24 R,W,(P) 5 ... 50°
Frequency difference f S25 R,W,(P) 0.02 ... 0.50 Hz
Operate time (dead time) t
VC
S26 R,W,(P) 0.10 ... 20 s
Check time in command mode operation, t
check
S27 R,W,(P) 0.05 ... 300 s
Closing signal length t
pulse
S28 R,W,(P) 0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker t
CB13
(stage 1) S29 R,W,(P) 0.05 ... 0.25 s
Operate time of circuit breaker t
CB23
(stage 2) S30 R,W,(P) 0.05 ... 0.25 s
Checksum of switchgroup SGF S31 R,W,(P) 0 ... 255
Checksum of switchgroup SGB S32 R,W,(P) 0 ... 255
Checksum of switchgroup SGR S33 R,W,(P) 0 ... 255
Second settings
Upper threshold voltage U
max
S41 R,W,(P) 0.50 ... 1.00 x U
n
Lower threshold voltage U
min
S42 R,W,(P) 0.10 ... 0.80 x U
n
Voltage difference U S43 R,W,(P) 0.02 ... 0.40 x U
n
Phase angle difference ∆ϕ S44 R,W,(P) 5 ... 50°
Frequency difference f S45 R,W,(P) 0.02 ... 0.50 Hz
Operate time (dead time) t
VC
S46 R,W,(P) 0.10 ... 20 s
Check time in command mode operation, t
check
S47 R,W,(P) 0.05 ... 300 s
Closing signal length t
pulse
S48 R,W,(P) 0.2 ... 20 s
(only in command mode operation)
Operate time of circuit breaker t
CB13
(stage 1) S49 R,W,(P) 0.05 ... 0.25 s
Operate time of circuit breaker t
CB23
(stage 2) S50 R,W,(P) 0.05 ... 0.25 s
Checksum of switchgroup SGF S51 R,W,(P) 0 ... 255
Checksum of switchgroup SGB S52 R,W,(P) 0 ... 255
Checksum of switchgroup SGR S53 R,W,(P) 0 ... 255