30
Data Code Data Value
direction
Control parameters
Resetting of recorded data V102 W 1 = registers are reset
Remote control of main and second settings V150 R,W 0 = main settings activated
1 = second settings
activated
Event mask for events of stage 1 V155 R,W 0 ... 255, see "Event codes"
Event mask for events of stage 2 V156 R,W 0 ... 255, see "Event codes"
Event mask for output signals V157 R,W 0 ... 255, see "Event codes"
Event mask for input signals V158 R,W 0 ... 255, see "Event codes"
Opening of password for remote setting V160 W 1 ... 999
Changing or closing of remote setting password V161 W,(P) 0 ... 999
Activation of self-supervision function V165 W 1 = self-supervision output
activated and IRF
LED indicator
switched on
LED indicator test V166 W,(P) 0 ... 15
Final factory test V167 W,(P) 1 = display segment test
2 = initialization of
EEPROM and power
reset
Internal fault code V169 R 0 ... 255
Data communication address of the module V200 R,W
Data transfer rate V201 R,W 4800 or 9600 Bd (R)
4.8 or 9.6 kBd (W)
Program version V205 R 076_
Reading of event register L R Time, channel number
and event code
Re-reading of event register B R Time, channel number
and event code
Type designation of the relay module F R SPCU 3D45
Reading of module status data C R 0 = normal status
1 = module been subject
to automatic reset
2 = overflow of event
register
3 = events 1 and 2 together
Resetting of module status data C W 0 = resetting
Time reading or setting T R,W 00.000 ... 59.999 s
Explanations:
R = data to be read from the relay module
W = data to be written to the relay module
(P) = writing allowed through a password
SC13 synchro-check function of stage 1
SC23 synchro-check function of stage 2
VC13 voltage-check function of stage 1
VC23 voltage-check function of stage 2