32
Data Code Data Values
direction
Checksum of switchgroup SGF1, S49 R, W (P) 0...255
second setting
Checksum of switchgroup SGF2, S50 R, W (P) 0...255
second setting
Checksum of switchgroup SGB, S51 R, W (P) 0...255
second setting
Checksum of switchgroup SGR1, S52 R, W (P) 0...255
second setting
Checksum of switchgroup SGR2, S53 R, W (P) 0...255
second setting
Checksum of switchgroup SGR3, S54 R, W (P) 0...255
second setting
Operate time for the circuit breaker S61 R, W (P) 0.1...1.0 s
failure protection
RECORDED AND MEMORIZED PARAMETERS
Current on phase L1 at starting V11...V51 R 0...63 x I
n
or operation
Current on phase L2 at starting V12...V52 R 0...63 x I
n
or operation
Current on phase L3 at starting V13...V53 R 0...63 x I
n
or operation
Neutral current I
0
at starting V14...V54 R 0...21 x I
n
or operation
Duration of the latest start V15...V55 R 0...100%
situation of stage I>
Duration of the latest start V16...V56 R 0...100%
situation of stage I>>
Duration of the latest start V17...V57 R 0...100%
situation of stage I
0
>
Duration of the latest start V18...V58 R 0...100%
situation of stage I
0
>>
Maximum demand current for 15 min. V1 R 0...2.5 x I
n
Number of starts of stage I> V2 R 0...255
Number of starts of stage I>> V3 R 0...255
Number of starts of stage I
0
> V4 R 0...255
Number of starts of stage I
0
>> V5 R 0...255
Phase conditions during trip V6 R 1 = I
L3
>, 2 = I
L2
>,
4 = I
L1
>, 8 = I
0
>
16 = I
L3
>>, 32 = I
L2
>>
64 = I
L1
>>,128 = I
0
>>
Operation indicator V7 R 0...9
Highest maximum demand current V8 R 0…2.55 x I
n
15 minute value
CONTROL PARAMETERS
Resetting of output relays V101 W 1 = output relays and all
at latched output information from the
display are reset
Resetting of output relays V102 W 1 = output relays and
and recorded data registers are reset