TMD-T4 protocol communication - instruction manual IM148-U-AB v0.92 pag. 8 / 12
REPORT SLAVE ID (Function Code $ 11)
This function returns the type of the instrument and the current status of the slave run indicator. Broadcast is not
supported. The Query and the Response messages are the following:
QUERY:
START OF
FRAME
ADDRESS
FIELD
FUNCTION
CODE
ERROR
CHECK
END OF
FRAME
START OF FRAME = Starting message marker.
ADDRESS FIELD = TMD device address (01...F7 HEX) (1 byte).
FUNCTION CODE = Operation code ( 11 HEX) (1 byte).
ERROR CHECK = Check sum.
END OF FRAME = End message marker.
RESPONSE:
START OF
FRAME
ADDRESS
FIELD
FUNCTION
CODE
BYTE
COUNT
SLAVE
ID
RUN
INDICATOR
STATUS
ADDITIONAL
DATA
ERROR
CHECK
END OF
FRAME
START OF FRAME = Starting message marker.
ADDRESS FIELD = TMD device address (01...F7 HEX) (1 byte).
FUNCTION CODE = Operation code ( 11 HEX) (1 byte).
BYTE COUNT = Number of data bytes (0A HEX) (1 byte).
(here start DATA field)
SLAVE ID = Slave ID identifier (54 HEX) (1 byte).
RUN INDICATOR STATUS = Run indicator status (FF HEX) (1 byte).
ADDITIONAL DATA = 8 Data bytes to compose the follow Hex string.
[0x24] [0x43] [0x74] [0x74] [0x36] [0x73] [SW rev HI][SW rev LO]
ERROR CHECK = Check sum.
END OF FRAME = End message marker.
The normal response has the slave ID identifier (54 HEX) and the run indicator status (FF HEX) plus 8 data bytes
(byte count is 10, 0A Hex). Last two data bytes carry firmware version (bytes 11 and 12 of the frame ).