6. Assembly of the switchgear at site
Dimension chart of structural data - panels 12 / 17.5 kV
Panel width FT
[mm] 650 800 1 000
Aisle width G
(1)
[mm] 1 150 1 300 1 500
Switchgear room door width [mm] 850 1 000 1 200
Switchgear room door height
(2)
[mm] 2 400 2 400 2 400
Opening in ceilning if transported through roof
Width
[mm] 1 000 1 000 1 200
Length [mm] 1 500 1 500 1 500
Ceiling load
(3)
[kg/m
2
] 1 200 1 400 1 400
(1) Minimum dimensions. Pay attention to appropriate national standards.
(2) Applies to low voltage compartments of standard height
(3) Approximate numbers depending on the type of panels
Dimension chart of structural data - panels 24 kV
Panel width FT
[mm] 800 1 000
Aisle width G
(1)
[mm] 1 300 1 500
Switchgear room door width [mm] 1 000 1 200
Switchgear room door height
(2)
[mm] 2 525 2 525
Opening in ceilning if transported through roof
Width
[mm] 1 000 1 200
Length [mm] 1 800 1 800
Ceiling load
(3)
[kg/m
2
] 900 850