6. Assembly of the switchgear at site
Figure 54: UniGear ZS1 24 kV. Guideline structural data for foundation frame on concrete floor It is not valid for the panel with
switch-disconnector.
C Typical panel depth C = 1 700 mm (For short-time
current up to 25 kA, 1 560 mm depth version is available)
- however always consider annotation 2)
G Width of operating aisle ("6.2 Foundations")
FT Panel width ("6.2 Foundations")
TB Door width = FT + 200 mm
TH Door height = panel height + 200 mm
1 Rear cover
2 Door
3 Side end cover
4 Screw
5 Steel dowel
1) Minimum dimensions; recommended space 500 mm.
2) Dimension must be verified in documentation of the relevant
order