6. Assembly of the switchgear at site
Busbar compartment access
Access to the busbar compartment is possible
either from the top of the panel after
dismounting the pressure relief plate before the
mounting of the gas duct, or from the front of the
circuit-breaker compartment.
After circuit-breaker has been withdrawn from
the panel, it is possible to dismount the
horizontal partition 1 by unscrewing 4 screws
holding the partition from the inside. After that,
the partition can be dismantled and taken out of
the panel, which makes access to busbars from
the circuit-breaker compartment possible.