5 - Installation
Once the phase of mechanical installation of the METER is nished,
it is necessary to congure the METER in order to make it compatible
with the inverter. Set the parameters on the meter display as set out in
the table:
Parameter Settings
Address 1
Protocol MODBUS
Baud rate 57600
Parity EVEN
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds to access the setup menu of the meter.
2. Press repeatedly until the display shows “Set”.
- Press to conrm.
3. Press repeatedly until the display shows “RS-485”.
- Press to conrm.
4. Press repeatedly until the display shows “Protocol”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly until the display shows “Modbus”.
- Press to conrm the change.
- Press for two seconds to return to the RS485 menu.
5. Press repeatedly until the display shows “Baud rate”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 57600.
- Press to conrm the change.
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly until the display shows “Address”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 1.
- Press to conrm the change.
- Press for two seconds to return to the RS485 menu.
7. Press repeatedly until the display shows “Modbus”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select even.
- Press to conrm the change.