EasyManua.ls Logo

ABB V-Contact VSC7/P

ABB V-Contact VSC7/P
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
54
55
58
51
52
53
32
61
61
Fig. 20a
Fig. 20b
a) Mounting the adapters (fig. 20a)
Thefuseholder(32)(fig.20b)ispresettotakefuseswithfixing
centredistanceof553mm.Forsmallersizes,threeadapters
areneeded,asindicatedbelow:
– adapter(51)forfuseswithfixingcentredistance
l = 235 mm
– adapter(52)forfuseswithfixingcentredistance
l = 305 mm
– adapter(53)forfuseswithfixingcentredistance
l = 454 mm.
Selectthetypeofadapter,fixitontothefuseonthestriker
sidebymeansofthegrubscrews(54),thecupsprings(55)
andtheshortnuts(58).Mounttheadapterwiththeextension,
with the cap facing the striker.
The same instructions are given in the Kit sheet put in the
adapter packing.
Only position the grub screws (54) as shown
in the drawing.
b) Mounting the fuses (fig. 20b)
Mountthefusesortheadapter(preassembledasindicated
inpar.a)withthestriker,(indicatedbythearrow)facingthe
opposite side to the one of the contactor tulips and fix them
bymeansofthescrews(56)andthespringwashers(57).
c) Dismantling the fuses
Todismantlethefusesandrelativeadapters,proceedin
reverse order to par. b) and a).
d) Assembling and dismantling the VSC/PN and VSC/PNG
contactor fuses
It is also possible to use BS fuses with double cartridge
connected in parallel in the VSC/PN and VSC/PNG contactors
(fig.20c)andthereforeinserieswiththecontactor.The
assembly and dismantling operations are the same as what
isdescribedinsectionsa),b)andc)above,withtheonly
difference being to handle a pair of fuses per phase at the
sametime(fig.20c)connectedbymeansofasuitable
adapter.
Striker side
Fig. 20c