Advant Controller AC 31 / Issued: 01.99 3 – 1 Technical specifications
3
3 Technical specifications
This chapter describes the products and their general characteristics and operating conditions.
3.1 General operating conditions
The AC31 units were developed in accordance with the European EC directives, the main
national and international IEC 1131-1- and IEC 1131-2 standards and the EN61131-2 product
standard concerning automation devices.
Ambient conditions
- Temperature:
operation: horizontal
vertical
storage
transport
0 °C to + 55 °C
0 °C to + 40 °C
- 40 °C to + 75 °C
- 25 °C to + 75 °C
- Humidity
annual average
up to 30 days per year
occasionally
DIN 40040 class F without condensation
75%
95%
85%
- Atmospheric pressure:
operation
storage
800 hPA ( 2000 m)
600 hPA ( 3500 m)
Mechanical data
- Degree of protection index
- Housing
- Vibration stress
- Shock stress
IP20
UL V2
CEI68-2-6 Test Fc
CEI68-2-27 Test Ea
Tolerances for mains voltages
- 24 V d.c.
- 120 V a.c. (50/60 Hz)
- 230 V a.c. (50/60 Hz)
19.2 to 30 V (- 20%, + 25%)
97.75 to 126.5 V (- 18.5%, + 5.5%)
195.5 to 253 V (- 15%, + 10%)