Programming 5 – 10 Advant Controller AC 31 / Issued: 01.99
3
Initialization: word flags
Õ Absolute identifier: KW 00,02
Õ Symbolic identifier: INIT_MW
Value n of the system constant KW 00,02
Word flag areas which are initialized (set
to 0)
n = 0 (default) MW 000,00...MW 099,15
MW 230,00...MW 255,15
n = 1...99 MW n,00...MW 099,15
MW 230,00...MW 255,15
n = 100...229 MW 230,00...MW 255,15
n = 230...255 MW n,00...MW 255,15
n < 0, n > 255 No initialization
Initialization: double word flags
Õ Absolute identifier: KW 00,03
Õ Symbolic identifier: INIT_MD
Value n of the system constant KW 00,03
Double word flag areas which are
initialized (set to 0)
n = 0 (default) MD 000,00...MD 001,15
n = 1 MD 001,00...MD.001,15
n < 0, n > 1 No initialization
Initialization: step chains
Õ Absolute identifier: KW 00,04
Õ Symbolic identifier: INIT_S
Value n of the system constant KW 00,04
Step chains which are initialized (set
to 0)
n = 0 (default) S 000,00...S 125,15
n = 1...125 S n,00...S 125,15
n < 0, n > 125 No initialization
Initialization: historical values
Õ Absolute identifier: KW 00.05
Õ Symbolic identifier: INIT_VW
Value n of the system constant KW 00,05
Historical values which are initialized (set
to 0)
n = 0 (Default) Initialization of all historical values
n < 0,n > 0 No Initialization