COOLING ONLY (R22)
MODEL INDOOR UNIT RCM 61C
OUTDOOR UNIT
ALC 61C
NOMINAL kcal/h
14110
COOLING W 16410
CAPACITY Btu/h
56000
NOMINAL TOTAL POWER W
5593
NOMINAL TOTAL CURRENT A 9.4
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50
REFRIGERANT / CONTROL
R22 / CAPILLARY TUBE IN INDOOR
AIR FLOW cfm / L/s 1550 / 732
HIGH
56
MED
53
LOW
46
FAN MOTOR
2 x 4 POLES x 80 W
RATED INPUT POWER W
327
RATED RUNNING CURRENT A
1.40
MATERIAL
S.I.G.C
DIAMETER mm/in
9.52 / 3/8
THICKNESS mm/in
0.35 / 0.014
MATERIAL
ALUMINIUM
THICKNESS mm/in
0.11 / 0.0043
ROW
4
FIN PER INCH
14
FACE AREA
m
2
ft
2
0.42 / 4.51
HEIGHT mm/in
285 / 11.2
DIMENSION WIDTH mm/in 1874 / 73.8
DEPTH mm/in
666 / 26.2
WEIGHT kg
85
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION
LCD WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
CONDENSATE DRAIN SIZE mm/in
19.05 / 3/4
AIR FILTER WASHABLE SARAN NET
PACKING HEIGHT mm/in
368 / 14.5
DIMENSION WIDTH mm/in
1992 / 78.4
DEPTH mm/in 760 / 29.9
POWER SOURCE V/Ph/Hz
415 / 3 / 50
COMPRESSOR TYPE
SCROLL
CAPACITOR µF -
LOCK ROTOR AMP. A
74.0
RATED RUNNING CURRENT A
8.5
RATED INPUT POWER W
5008
PROTECTION DEVICE
OVERLOAD PROTECTION / HI-LO PRESSURE SWITCH
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL
GLASS R. ACRLY STYLENE RESIN
DIAMETER mm/in
600 / 24
RATED RUNNING CURRENT A
1.2
MOTOR OUTPUT W
400
RATED INPUT POWER W
258
MATERIAL
S.I.G.C
DIAMETER mm/in
9.52 / 3/8
THICKNESS mm/in
0.35 / 0.014
MATERIAL
ALUMINIUM (SLIT)
THICKNESS mm/in
0.127 / 0.005
ROW
3
FIN PER INCH 14
FACE AREA
m
2
ft
2
0.84 / 9.04
HEIGHT mm/in
850 / 33.5
DIMENSION WIDTH mm/in 1030 / 40.6
DEPTH mm/in
460 / 18.1
WEIGHT kg
108
MATERIAL ELECTRO GALVANIZED MILD STEEL
CASING THICKNESS mm/in
1.0 - 2.3 (0.0393 -0.0905)
FINISHING
EPOXY POLYESTER POWDER COATING
SOUND PRESSURE LEVEL dBA 61
TYPE
FLARE VALVE
SIZE LIQUID mm/in
12.7 / 1/2
GAS mm/in 19.05 / 3/4
PACKING HEIGHT mm/in
1016 / 40.0
DIMENSION WIDTH mm/in
1178 / 46.4
DEPTH mm/in 602 / 23.7
COIL FAN COMPRESSOR
OUTDOOR UNIT
PIPE
SOUND LEVEL (dBA)
TUBEFINTUBE
COIL
INDOOR UNIT
FAN
FIN
* not suitable for high ambient application
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER
5