INSTALLATION GUIDE
DWFX-F Installation Method
Health and safety
This process must be undertaken by competent per-
sons. More than one person may be required to ensure
the safe handling of large dampers and other materi-
als. Use must be made of access equipment to ensure
unsafe practices are not used to approach walls or dif-
cult access areas.
Standard site PPE should be used (minimum steel toe
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as dened by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
All waste materials should be collected and disposed of
as dened by the relevant supplier.
Actuators: All wiring should be carried out in accor-
dance with the wiring details provided by the IEE and
BS regulations and by a competent person. Care must
be taken when installing and inspecting dampers, as
they are likely to close without warning due to loss of
electrical power or a temperature rise in the ductwork.
This is their prime function. Do not insert any items,
ngers or limbs between the blades. Larger dampers
must be handled in accordance with current regula-
tions and good practice due to weight.
Drawings
Please visit our website to download the installation dra-
wings, which are located on the relevant product down-
load section.
Applies to...
Actionair SmokeShield PTC
Actionair FireShield
Contents
Drawings ............................................. 1
Applies to ............................................. 1
Health and safety .................................. 1
CE Installation Method Overview ............... 2
Vertical Damper Installation in Plasterboard
Walls ...................................................3
Vertical Damper, Alblative Batt in a
Plasterboard Wall ................................... 4
Vertical Damper Installation (Top Flange
removed) in a Plasterboard Wall under
Concrete Slab ........................................5
Vertical Damper Installation in Masonry Walls
6
Vertical Damper, Ablative Batt in Masonry
Walls ................................................... 7
Vertical Damper (with a Pattress) in a
Masonry Wall ........................................8
Vertical Damper in a Masonry Wall against
slab ....................................................9
Periodic maintenance ............................. 10
Actuators ............................................ 11
Control Mode Installation Procedure .............................11
Wiring Diagrams .......................................................... 12
DWFX-F Damper Dimensional Data ............13
Actionair SmokeShield PTC .......................................... 13
Actionair FireShield ...................................................... 15
Inspection and handover check sheet .........16