Industrial Electronic Devices
ADFweb.com S.r.l.
Document code: MN67044_ENG Revision 2.100 Page 29 of 37
Data type F:
2
2
2
2
2
2
2
2
2
2
2
2
2
21
2
2
2
2
2
22
2
2
2
2
2
2
2
2
2
2
2
2
Min (0 … 59);
Hour (0 … 23);
Day (1 … 31);
Month (1 … 12);
Year (0 … 99);
Time Invalid (0=Valid, 1=Invalid);
Summer Time (0=Standard Time, 1=Summer Time);
Reserved (0).
Data type G:
2
2
2
2
2
2
2
2
2
2
2
2
2
21
2
2
Day (1 … 31);
Month (1 … 12);
Year (0 … 99).
For example, if you have defined:
• Type of Data= Energy (J);
• Function Field=Instantaneous Value;
• Dimension= 32 bit;
• Modbus Register=150 (Register 151 declared implicitly because the dimension is 32 bit);
• Modbus Re Scale=152.
After the request, in Modbus register 150 you read 0x0004, in 151 you read 0x5678 and in register 152 is write 0x0006. The value
obtained is: 284280 x10
(6)
J.