Field-Wiring the Modules
,QVWDOODWLRQ
Unimode 400 Installation PN 50710:A 10/22/97 2-31
)LHOG:LULQJWKH$X[LOLDU\5HOD\0RGXOH$50
2YHUYLHZ
This section provides terminal assignments for ARM-4 module control relays K1-K4,
which control nonpower-limited circuits. Wiring requirements follow:
1RWH )RU PRUH LQIRUPDWLRQ
UHIHU WR $ SSHQGL[ ) 8/
3R ZHUOLPLW HG :LULQJ
5HTXLUHPHQWV
• Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet.
• All power-limited circuit wiring must remain at least 0.25 in. away from any
nonpower-limited circuit wiring.
• All power-limited and nonpower-limited circuit wiring must enter and exit the
cabinet though different knockouts, conduits, or both.
Table 2-11 contains contact ratings for relays K1-K4 on the ARM-4 module:
Table 2-11 Contact Ratings for K1-K4 on the ARM-4 Module
$50 7HUPLQDO
$VVLJQPHQWV
Figure 2-43 shows terminal assignments for control relays on the ARM-4 module:
)LJXUH $50 0RGXOH 7HUPLQDO $VVLJQPHQWV
Resistive Load
Contacts
N.O. N.C.
125 VAC 20 A 10 A
30 VDC 20 A 10 A