CM1-SERIES
aOls :Analogue Output relative
Low Scale
Ex. Output range set to be A4-20
(4~20mA) is relative to display
0~99.99;User can set the [aOls]
(Ao.LS) to be 2)00,At meantime, the
output signal will be 4mA
Setting Range: -1999~9999
(CM1-RL/CM1-F:-19999~99999)
Default: [ lOsc]: 0.00, [ hIsc]: 9(99;
Changed: [ aOls]: 20.00(Relative Low),
[ aOhs]: 80.00 (Relative High)
aOhs :Analogue Output relative
High Scale
Ex. Output range set to be A4-20
(4~20mA) is relative to display
0~99.99;User can set
the [aOhs] (Ao.HS) to be 8)00,At
meantime, the output signal will be 20mA。
Setting Range: -1999~9999
(CM1-RL/CM1-F:-19999~99999)
aOzro :Fine Zero Adjustment for
Analog Output;
Users can get Fine zero Adjustment for
analogue output by front key. Please
connect standard meter to the terminal of
analogue output for measuring the output
value. To press the front key(up or down
key) to adjust and check the output of
meter.。
Setting Range: -1999~9999
aOspn :Fine Span Adjustment for
Analog Output;
Users can get Fine span Adjustment for
analogue output by front key of the meter as
like as [aOzro] (Ao.Zro).
Setting Range: -1999~9999
ZSclr :Clear Fine Zero / Span
Adjustment for Analog Output
Programmable:
none(None): Do not clear
aOzro(Ao.Zro): Clear low adjust
aOspn(Ao.SPn): Clear high adjust
both(both): Clear low & high
adjust