CM1-SERIES
19 / 28
Rev 1.3
2018-07-02
D2
aOls
)0
000)0
50)0
aOls :Analogue Output relative
Low Scale
Ex. Output range set to be A4-20
(4~20mA) is relative to display
0~99.99User can set the [aOls]
(Ao.LS) to be 2)00At meantime, the
output signal will be 4mA
Setting Range: -1999~9999
(CM1-RL/CM1-F:-19999~99999)
Shift
Up
Down
Enter
Default: [ lOsc]: 0.00, [ hIsc]: 9(99;
Changed: [ aOls]: 20.00(Relative Low),
[ aOhs]: 80.00 (Relative High)
0.00%
100.00%
50.00%
OUTPUT
SCALE
9(99
[ hIsc]
)00
[ lOsc]
5)00
2)00
[ aOls]
8)00
[ aOhs]
D3
aOhs
199(9
199(9
150)0
aOhs :Analogue Output relative
High Scale
Ex. Output range set to be A4-20
(4~20mA) is relative to display
0~99.99User can set
the [aOhs] (Ao.HS) to be 8)00At
meantime, the output signal will be 20mA
Setting Range: -1999~9999
(CM1-RL/CM1-F:-19999~99999)
Shift
Up
Down
Enter
D4
aOzro
0
00000
`999
aOzro :Fine Zero Adjustment for
Analog Output
Users can get Fine zero Adjustment for
analogue output by front key. Please
connect standard meter to the terminal of
analogue output for measuring the output
value. To press the front key(up or down
key) to adjust and check the output of
meter.
Setting Range: -1999~9999
Shift
Up
Down
Enter
D5
aOspn
0
00000
9999
aOspn :Fine Span Adjustment for
Analog Output
Users can get Fine span Adjustment for
analogue output by front key of the meter as
like as [aOzro] (Ao.Zro).
Setting Range: -1999~9999
Shift
Up
Down
Enter
D6
ZSclr
none
none
both
ZSclr :Clear Fine Zero / Span
Adjustment for Analog Output
Programmable:
none(None): Do not clear
aOzro(Ao.Zro): Clear low adjust
aOspn(Ao.SPn): Clear high adjust
both(both): Clear low & high
adjust
&
Cycle selection
Enter